Table 15: Ambient data
Ambient data
Enclosure rating IP 66 (IEC 60529)
IP 67 (IEC 60529)
IP 69K (IEC 60529)
Ambient operating tempera‐
ture
0°C … +55°C
Storage temperature –25°C ... +75°C
Relative humidity 5 … 95%
Shock resistance 30g, 11ms (IEC 60068-2-27)
Vibration resistance 10Hz … 55Hz (IEC60068-2-27)
9.2 Response time
The response time is subject to the following parameters
Switching safety outputs on or off
Number of cascaded devices
Response time for switching off the safety outputs
Response time for single safety locking device: 100ms
Response time for cascade: 50ms +50ms * number of safety locking devices in
cascade
Response time for switching on the safety outputs
Response time for single safety locking device: 600ms
Response time for cascade: 575ms +25ms * number of safety locking devices
in cascade
9.3 Course of the output signal switching device test over time
The safety locking device tests the OSSDs for self-diagnosis at regular intervals.
To do this, the safety locking device switches each output signal switching device
briefly (for max. 600μs) to the OFF state and checks whether this channel is
voltage-free during this time.
Make sure that the machine’s control does not react to these test pulses and the
machine does not switch off.
1
Every 22ms
2
Every 11s