6 Electrical installation
6.1 Notes on cULus
The following conditions must also be fulfilled in order to use and apply the equipment
in accordance with UL508 requirements:
•
The voltage supply must conform to Class2 according to UL508.
•
Connections In 1 and In 2 must conform to Class 2 according to UL508.
•
The required fuse protection for each device is 1A. In a safe series connection, a
suitable device fuse protection must be calculated.
6.2 Device connection (M12, 8-pin)
Important information
DANGER
Incorrect connection of the safety locking device
Loss of safety function
b
In the case of insulating material/connection strands, observe the necessary
temperature resistance and mechanical load capability.
b
Only use safe contacts for safety functions.
Prerequisites
•
Mounting is completed.
•
Electrical installation is carried out according to the project planning.
•
Dangerous condition of the machine is and remains off during the electrical instal‐
lation.
•
Outputs of the device have no effect on the machine during electrical installation.
•
With insulation material or connection slots, pay attention to the temperature
resistance and mechanical load capability. For safety functions, use only safe
contacts.
Figure 19: Device connection (male connector, M12, 8-pin, A-coded)
Device connection (M12, 8-pin)
Table 2: Pin assignment for device connection (male connector, M12, 8-pin, A-coded)
Pin Wire color
1)
Designation Description
1 White Out AUX Application diagnostic output
(not secure)
2 Brown +24VDC Voltage supply 24VDC
3 Green Lock Lock input
4 Yellow In 2 OSSD 2 input
2)
5 Gray Output signal switching device
(OSSD) 1
Output OSSD 1
6 Pink Output signal switching device
(OSSD) 2
Output OSSD 2
ELECTRICAL INSTALLATION 6
8019972/1CS1/2022-07-20 | SICK O P E R A T I N G I N S T R U C T I O N S | TR10 Lock
23