EasyManua.ls Logo

SICK TR10 Lock - Page 26

SICK TR10 Lock
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55
44
3
3
2
2
1
1
5
6 7
8
4
321
Figure 21: Internal circuitry: T-connector for cascade
5
4
3
2
1
Figure 22: Internal circuitry: Terminator plug for cascade
DANGER
Bypassing the protective device
The dangerous state may not be stopped in the event of non-compliance.
If T-connectors are used for the cascade, mount connecting cables in such a way that a
single T-connector (and therefore a safety locking device) cannot be jumpered easily.
NOTE
In the case of safety locking devices cascaded with T-connectors, the application diag‐
nostic output cannot be evaluated.
Cascade connection (M12, 5-pin)
The 5-pin male connector of the last T-connector before the safe evaluation unit is the
interface between the cascade and the safe evaluation unit.
12
3 4
5
Figure 23: Cascade connection (M12, 5-pin, A-coded, male connector)
Table 4: Pin assignment for cascade connection (male connector, M12, 5-pin, A-coded)
Pin Wire color
1)
Designation Description
1 Brown +24VDC Voltage supply 24VDC
2 White Output signal switching device
(OSSD) 1
Output OSSD 1
3 Blue 0V Voltage supply 0VDC
6 ELECTRICAL INSTALLATION
26
O P E R A T I N G I N S T R U C T I O N S | TR10 Lock 8019972/1CS1/2022-07-20 | SICK
Subject to change without notice