Table 3: Switching behavior of the door application diagnostic output
Actuator Door application diagnostic output
Actuator not in response range OFF
Actuator in response range ON
Locking function application diagnostic output (Out AUX LOCK)
The signal of the locking function application diagnostic output changes as soon as the
locking function has been activated. This is not a safety output.
Table 4: Switching behavior of the locking function application diagnostic output
Locking function Locking function application diagnostic output
Locking function active ON
Locking function not active OFF
Fault application diagnostic output (Out AUX DIA)
The signal of the fault application diagnostic output changes as soon as a fault occurs.
This is not a safety output.
Table 5: Switching behavior of the fault application diagnostic output
Fault Fault application diagnostic output
Fault has occurred ON
No fault OFF
4.4.4 Switching behavior
Table 6: Switching behavior
Figure 13: Protective device
closed and locked
Figure 14: Protective device
closed but not locked
Figure 15: Protective device
open
Activating the locking func‐
tion
ON OFF Not relevant
OSSDs ON OFF OFF
Out AUX LOCK ON OFF OFF
Out AUX DOOR ON ON OFF
4.4.5 Safe series connection
OSSDs of several safety locking devices can be connected by safe series connection.
The connected OSSDs act like the OSSDs of a single device.
PROJECT PLANNING 4