11.2 Connecting cables
Requirements for the connecting cables
Table 22: Requirements for the connecting cables
Parameter Value
Min. wire cross-section 0.25 mm²
R max. 60 Ohm/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type = LIYY 8 x 0.25 mm² or 5 x 0.34 mm²
Maximum cable lengths
Table 23: Maximum cable lengths
Max. number of safety lock‐
ing devices
Possible output current per
OSSD (mA)
Max. length of cable from the
last safety locking device to
the controller (m)
5 10 150
25 100
50 80
100 50
150 25
6 10 120
25 90
50 70
100 50
150 25
10 10 70
25 60
50 50
100 40
150 25