Table 11: Device connection pin assignment (male connector, M12, 8-pin, A-coded)
Pin Wire color
1)
Designation Description
1 White Out AUX DOOR Door application diagnostic out‐
put (not safe)
2 Brown 24 V DC Voltage supply 24 V DC
3 Green MAG +24 V DC Magnet activation 24 V DC
4 Yellow Out AUX DIA Fault application diagnostic out‐
put (not safe)
5 Gray OSSD 1 Output OSSD 1
6 Pink OSSD 2 Output OSSD 2
7 Blue 0 V Voltage supply 0 V DC
8 Red Out AUX LOCK Locking device application diag‐
nostic output (not safe)
1)
Applies to the extension cables recommended as accessories.
Figure 31: Device connection (male connector, M12, 5-pin, A-coded)
Table 12: Device connection pin assignment (male connector, M12, 5-pin, A-coded)
Pin Wire color
1)
Designation Description
1 White NO 1 Pushbutton 1 output (normally
open)
2 Brown LED 1 LED 1 input
3 Green NO 2 Pushbutton 2 output (normally
open)
4 Black LED 2 LED 2 input
5 Gray RST Hardware reset connection
1)
Applies to the extension cables recommended as accessories.
6.4 Connection of a safe series connection
Overview
A maximum of 20 devices can be activated in series. The safe series connection can be
implemented using special T-connectors and an end connector. The safe evaluation
unit switches off the machine if a protective device is opened or a fault occurs at a
safety locking device.
Important information
NOTE
•
The locking device control (MAG 0 V DC), the application diagnostic outputs door
(Out AUX DOOR) and error application diagnostic outputs have to be wired sepa‐
rately.
•
In the case of safety locking devices cascaded with T-connectors, the locking
device application diagnostic output (Out AUX LOCK) cannot be evaluated.
•
Mount the connecting cable so that individual T-connectors (and thus a safety
locking device) cannot be easily jumpered.
6 ELECTRICAL INSTALLATION
32
O P E R A T I N G I N S T R U C T I O N S | TR110 Lock 8023119/15LY/2019-10-28 | SICK