53.2 错误诊断表格
LED 指示灯 / 故障界面 /
LED indicator/fault pattern
原因 /
Cause
措施 /
Measures
绿色 LED 未亮起 /
Green LED does not light up
无电压或电压低于极限值 /
No voltage or voltage
below the limit values
检查电源,检查整体电气连
接(导线和插头连接) /
Check the power supply,
check all electrical
connections (cables and
plug connections)
绿色 LED 未亮起 /
Green LED does not light up
电压中断 /
Voltage interruptions
确保电源稳定无中断 /
Ensure there is a stable
power supply without
interruptions
绿色 LED 未亮起 /
Green LED does not light up
传感器损坏 /
Sensor is faulty
如果电源正常,则更换传感
器 /
If the power supply is OK,
replace the sensor
黄色 LED 亮起,光路中无物
体 /
Yellow LED lights up, no
object in the path of the
beam
传感器和背景之间的间距过
小 /
/ Distance between the
sensor and the background
is too short
降低开关距离,参见图 F /
Reduce the sensing range,
see graphic F
光路中有物体,黄色 LED 未
亮起 /
Object is in the path of the
beam, yellow LED does not
light up
传感器和物体之间的间距过
大或开关距离设置的过小 /
Distance between the
sensor and the object is too
long or sensing range is set
too short
增大开关距离,参见图 F /
Increase the sensing range,
see graphic F
54 技术数据
54.1 技术数据
WTT190L-Axxx
激光等级 1
开关距离 0.2 ... 3.0 m
1)
最大开关距离 0.2 ... 3.0 m
1)
光斑直径/距离 < 12.0 mm / 3,0 m
供电电压 U
B
DC 12 ... 30 V
输出电流 I
max.
≤ 100 mA
开关频率 AVG 1: 833 Hz, AVG
4: 500 Hz, AVG 16:
147 Hz, AVG 64: 38
Hz, AVG 256: 10
Hz
2)3)
4)
最长响应时间 AVG 1: 0.6 ms, AVG
4: 1 ms, AVG 16: 3.4
ms, AVG 64: 13 ms,
AVG 256: 51.4
ms
5)3)4)
模拟输出
4 mA ~ 20 mA (≤
300
W) / 0 V ~ 10 V
(≥10 kW) / 可切换
53 故障排除
96
8020032.17U4 | SICK
Subjec
t to change without notice