~ 39 ~
4.6.4 IRUN Pump running time
Setup steps:
To select submenu IRUN, “IRUN 15” displays on the
screen.
Press SET button, parameter 15 displays and
blinks, factory set is 15 seconds
Press + - button, to adjust time, adjustable range
5~ 120 seconds.
Press ESC button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
4.7 SFB Solid fuel boiler turn on/off
Description: Under SFB boiler is standby. If the tank temperature T3 drops below the
preset turn-on temperature of solid fuel boiler ( SFON), and temperature of solid fuel boiler
(T4) is between its minimum MIN3 and its maximum MAX3 ( MIN3< T4<MAX3), then
solid fuel boiler (P2) is triggered; when tank temperature T3 rises up to the preset turn-off
temperature of solid fuel boiler (SFOF),or when temperature of the solid fuel boiler(T4)
exceeds its MIN3 and MAX3 that is T4>MAX3, or T4<MIN3, then solid fuel boiler is
stopped.
Note: the preset MIN3 should be at least 1
o
C higher than the preset SFOF, for example: set
SFON is 50
o
C, SFOF is 55
o
Cthen MIN3 should be at least 1
o
C higher than SFON, namely
it is 56
o
C. Then when the tank temperature is below 50
o
C, solid fuel boiler is triggered, when
the tank temperature rises over 55
o
C, solid fuel boiler is stopped.
Setup steps:
To select submenu SFB, “SFB” displays on the
screen.
Press SET button, SFB OFF displays on the
screen.
Repress SET button, parameter OFF blinks, factory set is OFF
Press “SET button again to activate this function,
then SFB ON displays on the screen.
Press ESC button to exit the menu or wait for 20
seconds to exit automatically, parameters are saved
automatically.