~ 42 ~
Setup steps:
To select submenu DVWG, DVWG ----” displays on
screen. Default set is ----.
Press “SET” button, parameter“---- blinks on the
screen.
Repress “SET” button, function is triggered. And then 70
o
C blinks on the screen
Press + - button to adjust this temperature,
adjustable range is:(595℃)。
Press ESC button to exit the menu or wait for 20
seconds to exit automatically, parameters are saved
automatically.
4.8.2 COOL Tank cooling function
Description:
Tank high temperature cooling function is independent of solar systems operation, this
function is used to maintain the tank with a constant temperature, so extra energy in tank
will be transferred to other devices, to achieve this function, it is necessary to add a
electromagnetic valve or a circuit pump P2, its temperature is monitored by T3.
For example:
The set point of tank high temperature cooling function is 70
o
Cthen when tank temperature
(T2) rises up to 71
o
C, tank cooling function is activated, electromagnetic valve or circuit
pump and DT circuit pump (P1) are triggered at the same time; when tank temperature ( T2)
drops to 67
o
C electromagnetic valve or circuit pump and DT circuit pump (P1) are ceased
at the same time.
Setup steps:
To select submenu COOL, “COOL ---” displays on
screen.
Press “SET” button, ----blinks on the screen,
default set is ---.
Repress “SET” button, to activate cooling function, and COOL 95
o
C displays on the
screen, (“95
o
C blinks)