EasyManua.ls Logo

Siemens 181 - Page 22

Siemens 181
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
21
Parameter Value range Default Reconfiguration
in RUN
Scope with configuration
software, e.g.,
STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Temperature
coefficient
• Pt 0.00385055
• Pt 0.003916
• Pt 0.003902
• Pt 0.00392
• Pt 0.00385
• Ni 0.00618
• Ni 0.00672
• LG-Ni 0.005
• Cu 0.00427
Pt 0.00385055 Yes Channel Channel
Temperature
unit
• Degrees Celsius
• Degrees Fahrenheit
• Kelvin
Degrees Celsius Yes Channel Module
Reference
junction
4
• No reference channel mode
• Reference channel of the
module
• Internal reference junction
• Reference channel of
group 0 to 3
• Fixed reference
temperature
No reference
channel mode
Yes Channel Channel
Smoothing
• None
• Weak
• Medium
• Strong
None Yes Channel Channel
Interference
frequency
suppression
3
• 60 Hz
• 50 Hz
2
• 16.6 Hz
50 Hz Yes Channel Channel
Scalable
measuring
range
• Disable
• Enable
D
isable Yes Channel -
Measuring
range
resolution
• 2 decimal places
• 3 deci
mal places
2 decimal places Yes Channel -
Measuring
range center
• Value within the nominal
range of the measuring
range
0 Yes Channel -
Conductor
resistance
5
0 to 50000 mΩ 0 Yes C
hannel -