Parameters/address space
4.2 Parameters
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
22 Manual, 02/2014, A5E03573289-AD
Parameter Value range Default Reconfiguration
in RUN
Scope with configuration
software, e.g.,
STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Hardware
interrupt high
limit 1
3
• Disable
• Enable
D
isable Yes Channel -
High limit 1
3
• Value
8500 Yes Channel -
Hardware
interrupt low
limit 1
3
• Disable
• Enable
D
isable Yes Channel -
Low limit 1
3
• Value
-2000 Yes Channel -
Hardware
interrupt high
limit 2
3
• Disable
• Enable
D
isable Yes Channel -
High limit 2
3
• Value
8500 Yes Channel -
Hardware
interrupt low
limit 2
3
• Disable
• Enable
D
isable Yes Channel -
Low limit 2
3
• Value
-2000 Yes Channel -
Potential group
• Use potential group of the
left module
• Enable new potential
group
Use potential
group of the left
module
No Module Module
1
Diagnostics: Missing supply voltage L+: Detection per module or alarm per channel
2
Interference frequency suppression: Interfering signals at 400 Hz are automatically included in the filtering at 50 Hz.
3
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
configuration, the configuration options are restricted. If required, you can still assign these parameters using data
record 128 as described in the "GSD file PROFINET IO" column (see table above). The parameter length of the
I/O module is 24 bytes.
4
Only for configuration with PROFIBUS GSD file: The set reference junction is used with the additional parameter "Kx
Reference junction activated" in the case of "Enable". In the case of "Disable", "No reference channel mode" is used for
RTD and "Fixed reference temperature" is used for TC.
5
For 2-wire connection only
Note
Unused channels
"Deactivate" unused channels in the parameter assignment to improve the cycle time of the
module.
A deactivated channel always returns the value 7FFF
H
.