Parameter data record
A.1 Dependencies when configuring with GSD file
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
48 Manual, 02/2014, A5E03573289-AD
Measurement
type
Measuring range Temperature
coefficient
Reference junction Temperature unit Conductor
resistance
(3-wire
connection)
Cu 10 climatic Cu 0.00427 *
Thermal resistor
(2, 3, 4-wire
connection)
Pt100
Pt200
Pt500
Pt1000 standard
Pt 0.00385055
Pt 0.003916
Pt 0.003902
Pt 0.00392
Pt 0.00385
No reference
channel mode
Degrees Celsius
Degrees
Fahrenheit
Kelvin
x (with 2-wire
connection)
Ni100
Ni120
Ni200
Ni500
Ni1000 standard
Ni 0.00618
Ni 0.00672
LG-Ni 1000
standard
LG-Ni 0.005
Thermal resistor
(3-wire
connection)
Cu 10 standard Cu 0.00427 *
Thermocouple Type B, N, E, R, S,
J, L, T, K, U, C,
TXK
* R
eference channel
of the module
1
Internal reference
junction
Reference channel
of group 0, 1, 2, 3
2
Degrees Celsius
Degrees
Fahrenheit
Kelvin
*
Fixed reference
temperature
x = property is allowed, = property is not allowed, * = property is not relevant
1
Use of "Reference channel of the module":
- Channel 0 must be set as "Pt100 climatic" with temperature unit: "Degrees Celsius".
-For each TC channel of this module that i
s intended to use channel 0 as reference, "Reference junction" must be set to
"Reference channel of the module".
2
Use of "Reference channel of group 0, 1, 2, 3":
- An RTD channel must be set as "Pt100 climatic" with temperature unit: "Degrees Celsius".
- "Reference channel of group 0, 1, 2, 3" must be set as the "Reference junction" of this channel.
- There must only be one RTD channel with "Reference junction" = "Reference channel of group 0, 1, 2, 3" per group 0,
1, 2, 3 and IO device!
- For each TC channel in the IO device that is intended to use this reference, "Reference junction" must be set to
"Reference channel of group 0, 1, 2, 3".
- If the reference channel is on channel 0, it can also be used as "Reference channel of the module" at the same time.