Parameter data record
A.1 Dependencies when configuring with GSD file
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Manual, 02/2014, A5E03573289-AD
49
Configuring with a PROFINET GSD file
The table lists the properties and their dependencies on the measurement type for
PROFINET.
Table A- 2 Dependencies on the measurement type
Measurement type Scalable
measuring
range
Measuring range
resolution
Diagnostics
Underflow Overflow Wire break Missing
supply
voltage L+
Reference
junction
Deactivated * * * * * * *
Voltage * x x x
Resistor
(2, 3, 4-wire
connection)
* x x x x
Resistor PTC
(2-wire connection)
* x x
Thermal resistor
(2, 3, 4-wire
connection)
x 2 and 3 decimal
places
x x x x
Thermocouple x 2 and 3 decimal
places
x x x x x
1)
x = property is allowed, = property is not allowed, * = property is not relevant
1
Property is not relevant if "Fixed reference temperature" is used
Configuring with a PROFIBUS GSD file
The table lists the properties and their dependencies on the measurement type and
measuring range for PROFIBUS.
Measurement
type
Measuring
range
Temperature
coefficient
Slot
reference
junction
Temperature
unit
Diagnostics
Underflow
/ overflow
Wire
break
Missing
supply
voltage
L+
Reference
junction
Deactivated * * * * * * * *
Voltage ±50 mV,
±80 mV,
±250 mV,
±1 V
* * * x x
Resistor
(2, 3, 4-wire
connection)
150 Ω,
300 Ω,
600 Ω,
3 kΩ, 6
* * * x x x