Data Mapping UM353-1B
April 2012
6-18
Analog Indicator [ODA]
Code R/W Description Range Coil(MB)
L#P1AA R 1-Process 1 Alarm A is Active 1/0 00296+48(#-1)
L#P1AN R/W 1-Process 1 Alarm A is Not Acknowledged 1/0 00297+48(#-1)
L#P1AE R/W 1-Process 1 Alarm A is Enabled 1/0 00298+48(#-1)
L#P1BA R 1-Process 1 Alarm B is Active 1/0 00299+48(#-1)
L#P1BN R/W 1-Process 1 Alarm B is Not Acknowledged 1/0 00300+48(#-1)
L#P1BE R/W 1-Process 1 Alarm B is Enabled 1/0 00301+48(#-1)
L#P2AA R 1-Process 2 Alarm A is Active 1/0 00302+48(#-1)
L#P2AN R/W 1-Process 2 Alarm A is Not Acknowledged 1/0 00303+48(#-1)
L#P2AE R/W 1-Process 2 Alarm A is Enabled 1/0 00304+48(#-1)
L#P2BA R 1-Process 2 Alarm B is Active 1/0 00305+48(#-1)
L#P2BN R/W 1-Process 2 Alarm B is Not Acknowledged 1/0 00306+48(#-1)
L#P2BE R/W 1-Process 2 Alarm B is Enabled 1/0 00307+48(#-1)
L#OS1 R/W 1-Alarms - Out of Service 1/0 00308+48(#-1)
L#PB1 R/W PB1SW Input MD (*) 1/0 00309+48(#-1)
L#PB2 R/W PB2SW Input MD (*) 1/0 00310+48(#-1)
L#PB3 R/W PB3SW Input MD (*) 1/0 00311+48(#-1)
L#P3AA R 1-Process 3 Alarm A is Active 1/0 00312+48(#-1)
L#P3AN R/W 1-Process 3 Alarm A is Not Acknowledged 1/0 00313+48(#-1)
L#P3AE R/W 1-Process 3 Alarm A is Enabled 1/0 00314+48(#-1)
L#P3BA R 1-Process 3 Alarm B is Active 1/0 00315+48(#-1)
L#P3BN R/W 1-Process 3 Alarm B is Not Acknowledged 1/0 00316+48(#-1)
L#P3BE R/W 1-Process 3 Alarm B is Enabled 1/0 00317+48(#-1)
L#P4AA R 1-Process 4 Alarm A is Active 1/0 00318+48(#-1)
L#P4AN R/W 1-Process 4 Alarm A is Not Acknowledged 1/0 00319+48(#-1)
L#P4AE R/W 1-Process 4 Alarm A is Enabled 1/0 00320+48(#-1)
L#P4BA R 1-Process 4 Alarm B is Active 1/0 00321+48(#-1)
L#P4BN R/W 1-Process 4 Alarm B is Not Acknowledged 1/0 00322+48(#-1)
L#P4BE R/W 1-Process 4 Alarm B is Enabled 1/0 00323+48(#-1)
L#OS R/W 1-Alarms - Out of Service 1/0 00324+48(#-1)
L#CC R 1-Configuration has Changed 1/0 00325+48(#-1)
L#NA R/W 1-Unacknowledged Loop Event 1/0 00326+48(#-1)
L#AE R 1-Active Loop Event 1/0 00327+48(#-1)
* These bits indicate the status of the switch input MD. A write of a “1” will have the same effect as pressing and
releasing the button on the faceplate. If the action of the switch is sustained the switch will change position. If
the action is momentary, the switch will close for one scan cycle.