4 Installation
4.5.3 Assembly Overview
Fig. 26 Assembly overview
) Note
Discard all screws and nuts marked red!
4.5.4 Disassembling the Insulator Column Kit
Loosen the M16 nuts at the fixing point between the bracket 1.3 and the wooden beams 1.6.
Lift the three insulator columns in the kit with the crane and put them down onto the brackets 1.3 on a solid base
but do not disconnect the suspension tackle fom the insulator column kit.