5 Operation
m
6000 -
Σ
(n
i
k
i
)
i = 1
k
x
n
x
=
1000037b
ki Weighting factor for breaking current I
kx Weighting factor for breaking current l
x
n. Number of carried out interruptions at breaking current I
nx Number of remaining permissible interruptions at breaking
current l
x
.
Fig. 58 Formula for calculating the max. number of
permissible interruptions
The maximum number of interruptions still permissible with a given number of operations (with consequent wear)
already carried out can be calculated using the above equation.
For example:
The circuit-breaker with a rated short-circuit breaking current of 50 kA has performed 250 interruptions with
breaking currents of 3.15 kA, and 2 interruptions 20 kA.
How many interruptions at 40 kA are still permissible?
n
40
= = = = 10,7
6000 - (250 + 200)
520
6000 - (n
3.15
k
3.15
+ n
20
k
20
)
k
40
60 )
520
00 - (250
1 + 2
100
Fig. 59 Number of remaining permissible interruptions
at breaking current l
x
.
A total of 10 interruptions at 40 kA are still permissible.
79