Counting operating mode (CNT)
4.2 Parameters/address space
Digital input module DI 8x24VDC HS (6ES7131‑6BF00‑0DA0)
34 Manual, 03/2015, A5E35243810-AA
Parameters
Value range
Default
Configu-
ration in
RUN
Effective range with configuration
software
HSP0127 for STEP 7
(TIA Portal);
HSP0229 for STEP 7;
PROFINET IO GSD
file
PROFIBUS
DP GSD file
Reaction to violation of
a counting limit
Stop counting
Continue counting
Stop counting yes Channel Channel
Edge selection
At rising edge
At falling edge
At rising edge yes Channel Channel
Count direction
Up
Down
Up yes Channel Channel
Set output
Off (DQ = 0)
Off (DQ = 1)
Counter value between
comparison value 0 and 1
Counter value not be-
tween comparison value
0 and 1
Off (DQ = 0) yes Channel Channel
Setting function of the
DI
Digital input without func-
tion
Gate start/stop
Reverse direction
Digital input
without func-
tion
yes Channel Channel
Counter high limit
-2147483648...2147483647
2147483647
yes
Channel
Channel
Counter low limit -2147483648...2147483647 0 yes Channel
3
Start value
-2147483648...2147483647
0
yes
Channel
3
Comparison value 1
-2147483648...2147483647
10
yes
Channel
Channel
Comparison value 0
-2147483648...2147483647
0
yes
Channel
3
1
When configuring with HSP0229 for STEP 7 or with a GSD file, the operating mode is specified by selecting the module
name.
2
If your PROFIBUS Master supports the "Read / write data record" function, you can set this parameter for each channel
via data record 128.
3
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
configuration, the configuration options are restricted. If your PROFIBUS Master supports the "Read / write data record"
function, you can set this parameter via data record 128.