Counting operating mode (CNT)
4.2 Parameters/address space
Digital input module DI 8x24VDC HS (6ES7131‑6BF00‑0DA0)
34 Manual, 03/2015, A5E35243810-AA
Effective range with configuration
software
HSP0127 for STEP 7
(TIA Portal);
HSP0229 for STEP 7;
PROFINET IO GSD
file
Reaction to violation of
a counting limit
• Stop counting
• Continue counting
Stop counting yes Channel Channel
Edge selection
• At rising edge
• At falling edge
At rising edge yes Channel Channel
Count direction
• Up
• Down
Up yes Channel Channel
Set output
• Off (DQ = 0)
• Off (DQ = 1)
• Counter value between
comparison value 0 and 1
• Counter value not be-
tween comparison value
0 and 1
Off (DQ = 0) yes Channel Channel
Setting function of the
DI
• Digital input without func-
tion
• Gate start/stop
• Reverse direction
Digital input
without func-
tion
yes Channel Channel
Counter low limit -2147483648...2147483647 0 yes Channel —
3
3
3
When configuring with HSP0229 for STEP 7 or with a GSD file, the operating mode is specified by selecting the module
name.
If your PROFIBUS Master supports the "Read / write data record" function, you can set this parameter for each channel
via data record 128.
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
configuration, the configuration options are restricted. If your PROFIBUS Master supports the "Read / write data record"
function, you can set this parameter via data record 128.