Oversampling (OVS) operating mode
5.2 Parameters/address space
Digital input module DI 8x24VDC HS (6ES7131‑6BF00‑0DA0)
Manual, 03/2015, A5E35243810-AA
53
5.2.2
Parameters
In distributed mode, you can use the Oversampling operating mode on the PROFINET IO in
an ET 200SP system.
In addition to configuration via the configuration software, you can also configure parameters
in RUN mode (dynamic) via the user program. When assigning parameters in the user
program, use the "WRREC" instruction to transfer the parameters to the module using the
data records; refer to the section Parameter assignment and structure of parameter data
record for Oversampling operating mode (Page 75).
The following parameter settings are possible:
Table 5- 1 Configurable parameters in the Oversampling operating mode
Parameters
Value range
Default
Configura-
tion in RUN
Effective range with con-
figuration software
HSP0127 for STEP 7
(TIA Portal);
HSP0229 for STEP 7
Potential group
Use potential group of the
left module
Allow new potential group
Use potential
group of the left
module
no Module
Operating mode
1
DI / Oversampling
Counting
no Module
Sampling rate
2 Values per cycle
3 Values per cycle
...
32 Values per cycle
yes Module
Diagnostics
No supply voltage L+
Disable
Enable
Disable yes Module
Diagnostics
Short-circuit to ground
Disable
Enable
Disable yes Module