Oversampling (OVS) operating mode
5.2 Parameters/address space
Digital input module DI 8x24VDC HS (6ES7131‑6BF00‑0DA0)
Manual, 03/2015, A5E35243810-AA
53
In distributed mode, you can use the Oversampling operating mode on the PROFINET IO in
an ET 200SP system.
In addition to configuration via the configuration software, you can also configure parameters
in RUN mode (dynamic) via the user program. When assigning parameters in the user
program, use the "WRREC" instruction to transfer the parameters to the module using the
data records; refer to the section Parameter assignment and structure of parameter data
record for Oversampling operating mode (Page 75).
The following parameter settings are possible:
Table 5- 1 Configurable parameters in the Oversampling operating mode
Effective range with con-
figuration software
HSP0127 for STEP 7
(TIA Portal);
HSP0229 for STEP 7
Potential group
• Use potential group of the
left module
• Allow new potential group
Use potential
group of the left
module
no Module
Operating mode
1
• DI / Oversampling
• Counting
— no Module
Sampling rate
• 2 Values per cycle
• 3 Values per cycle
• ...
• 32 Values per cycle
— yes Module
Diagnostics
No supply voltage L+
• Disable
• Enable
Disable yes Module
Diagnostics
Short-circuit to ground
• Disable
• Enable
Disable yes Module