Counting operating mode (CNT)
4.3 Interrupts/diagnostic messages
Digital input module DI 8x24VDC HS (6ES7131‑6BF00‑0DA0)
Manual, 03/2015, A5E35243810-AA
47
The DI 8×24VDC HS digital input module supports diagnostic interrupts.
The module generates a diagnostic interrupt at the following events:
● Channel temporarily unavailable
● Short-circuit
● Parameter assignment error
● No load voltage
A diagnostic interrupt is output for each diagnostics event and the DIAG LED on the module
flashes. The diagnostic interrupts can, for example, be read from the diagnostics buffer of
the CPU. You can evaluate the error codes with the user program.
Table 4- 7 Diagnostic interrupts, their meaning and how to deal with them
Short-circuit to ground at encoder supply
Parameter assign-
ment error
10
H
• The module cannot evaluate parame-
ters for the channel.
• Incorrect parameter assignment.
Correct parameter assignment
No load voltage 11
H
No or insufficient supply voltage L+
• Check supply voltage L+ on the Ba-
seUnit
• Check BaseUnit type
Channel temporarily
unavailable
1F
H
Firmware update in progress or update
has been canceled.
The module reads no process values in
• Wait for firmware update.
• Restart the firmware update.