09.02  Parameter List 
Siemens AG    6SE7087-6AK85-1AA0 
5-5 
Rectifier/Regenerating Unit    Operating Instructions 
PNU 
 
*
 
: Conf. 
    Par. 
OP1S parameter name 
 
Description 
Value range  
[phys. unit] 
Selection text 
Display 
Indices 
Factory-
setting 
See 
Modify 
(access / 
status) 
r032 Line Frequency 
Display of the line frequency 
 
PNU=20Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.01 Hz,   
0 - 100% 
=
∧
 0 to 50 Hz PZD gr.: 1 
0.01 to 65.00 
[Hz] 
- 
- 
2/    BR 
r033 Firing Angle 
Display of the firing angle 
 
PNU=21Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.1 °el,  
0 - 100% 
=
∧
 0°el -180°el   PZD gr.: 1 
0.0 to 165.0 
[°el] 
- 
- 
2/    BR 
r034  DC Amps (set) 
Display of DC link current setpoint 
 
PNU=22Hex; Type=I2; Scaling: 1Hex 
=
∧
 0.1 %, ±100% 
=
∧
 ±P075 
  PZD gr.: 1 
-150 to 150 
[%] 
- 
- 
3/    BR 
r035  DC Amps (act) 
Display of actual DC link current 
 
PNU=23Hex; Type=I2; Scaling: 1Hex 
=
∧
 1 %, ± 100% 
=
∧
 ± P075 
  PZD gr.: 1 
-199 to 199 
[%] 
- 
- 
2/    BR 
r036  DC Volts (set) 
Display of DC link voltage setpoint 
The setpoint 1.35
*
r030, limited to values of P074 up to 106.8%. 
 
PNU=24Hex; Type=O2; Scaling: 1Hex 
=
∧
 1 %, 100% 
=
∧
 1.35
*
P071 
  PZD gr.: 1 
0 to 199 
[%] 
- 
- 
3/    BR 
r037  DC Volts (act) 
Display of actual DC link voltage 
 
PNU=25Hex;  Type=O2; Scaling: 1Hex 
=
∧
 1 %, 100% 
=
∧
 1.35
*
P071 
  PZD gr.: 1 
0 to 199 
[%] 
- 
- 
2/    BR 
r038  DC Volts Deviat. 
Display of setpoint/actual-value deviation of DC link voltage controller 
 
PNU=26Hex; Type=I2; Scaling: 1Hex 
=
∧
 1 %, 100% 
=
∧
 1.35
*
P071 
  PZD gr.: 1 
-199.9 to 199.9 
[%] 
- 
- 
3/    BR 
r039 AnalogOut Displ. 
Display of terminal X102-14 (analog output) 
 
PNU=27Hex; Type=O2; Scaling: 1Hex 
=
∧
 0.1, ± 100% 
=
∧
 ± 10V at terminal 
X102-14 
  PZD gr.: 1 
-112.1 to 112.1 
[%] 
- 
- 
2/    BR 
 