09.02  Options 
Siemens AG    6SE7087-6AK85-1AA0 
9-3 
Rectifier/Regenerating Unit    Operating Instructions 
How to install an LBA local bus adapter in the electronics box: 
-  Undo the two fixing screws on the CUR board 
and pull board out by special handles. 
-  Push LBA bus extension into electronics box 
(see picture on right for position) until it 
engages. 
-  Insert CUR board in left-hand board location 
again and tighten fixing screws in handles. 
Location 2 (Options)
Location 3 (Options)
Location 1 (CUD1)
 
 
Boards  Current drain (mA) 
24V DC supply 
CBC 100 
CBP2 130 
SCB1 50 
SCB2 150 
T100 550 
T300 without tacho  620 
T400 without tacho and 
terminal wiring 
400 
C
U
R
FD
EG
132
Arrangement of
board locations 1 to 3
and slots D to G in
electronics box
 
 
Current input of DC 24V power supply (X9): 
The figures are required in addition to the 1A 
consumed by the basic unit. 
Table 9.3  Current drain of the option boards 
 
9.2 Interface boards 
The boards listed in the following table must be installed externally and connected to the installation side (for 
start-up, see Section 4.4.4 “Procedure for commissioning the serial I/O board SCB1” and the description of the 
board). 
Desig-
nation 
Description  Order No. 
SCI1  Serial I/O board (only in conjunction with SCB1). 
Analog and binary input and outputs for  coupling to the 
SCB1 via fiber-optic cable 
Board 
description 
6SE7090-0XX84-3EA0
6SE7080-0CX84-0BC0 
SCI2  Serial I/O board (only in conjunction with SCB1) 
Binary inputs  and outputs for coupling to the  SCB1 via 
fiber-optic cable. 
Board 
description 
6SE7090-0XX84-3EF0
6SE7080-0CX84-0BC0 
Table 9.4  Interface boards 
 