09.02  Connection 
Siemens AG    6SE7087-6AK85-1AA0 
3-19 
Rectifier/Regenerating Unit    Operating instructions 
Pin assignment for interface cable X300: 
1
2
3
4
5
9
8
7
6
1
2
3
4
5
9
8
7
6
on PC, COMx: male
on cable: female
on 6SE70 device, X300: female
on cable: male
 
 
 
3.4  Measures for keeping to RFI suppression regulations 
So that you can observe the radio interference regulations, you must note the following points: 
•  Grounding 
  The converter necessarily generates radio interference as it functions. It is necessary to return them to 
source via a connection with as low resistance as possible (cross-sectional area of ground connection ≥ 
cross-sectional area of network connection). 
  Use the best grounding opportunity when installing the rectifier/regenerating unit and optional radio 
interference suppression filters (e.g. mounting plate, grounding cable, ground bus). Interconnect all 
conductive housings with a large contact surface. 
  For interference suppression not only the cross-sectional area (observe safety regulations in case of fault), 
but especially the contact surface is important because high-frequency interference currents do not flow 
through the entire cross-sectional area but mainly along the outside skin of a conductor. 
•  Shielding 
  To reduce interference and observe the radio interference suppression levels,  
-  shielded cable must be used between the converter output and the motor and 
-  shielded control cables laid. 
The shield must be connected to ground potential at both ends. 
•  Filters 
  The radio interference filters must be connected before the infeed unit. The housings must be 
interconnected conductively. 
To observe the radio interference suppression regulations, A1 interference suppression filters are 
recommended. 
 
NOTICE 
Perform hipot tests on systems with radio interference suppression filters with direct voltage because of the 
filter capacitors! 
Control cables that are directly connected with the converter are always shielded so that the highest possible 
interference immunity is achieved. The shield must be grounded at both ends. 
To avoid coupled interference, control cables directly connected to the device must be routed separately from 
power cables. Minimum distance 20 cm. 
If converters are installed in systems by authorized workshops, interference immunity can be ensured by other 
suitable wiring practices. 
See also "SIMOVERT MASTERDRIVES Installation instructions for design of drives in conformance with EMC 
regulations“ under "Documentation" on the DriveMonitor CD-ROM of the inverter or converter "compendium" 
Chapter 3. 
 