09.02  Options 
Siemens AG    6SE7087-6AK85-1AA0 
9-5 
Rectifier/Regenerating Unit    Operating Instructions 
A few seconds after initialization of the OP1S, the display 
automatically switches to the operating display. 
From the operating display, you can enter the basic menu by 
pressing the <P> key. Here either "free access" to all parameters 
or different functions can be selected. Details of the functions can 
be found in the OP1S operating instructions. 
In the state "free access", parameterization of the device is 
possible. 
If you press the <R> key (several times if necessary), you can 
return to the operating display. 
Operating display
Basic menu
Free access
<P>
<P> <R>
<R>
 
 
With SIMOVERT 6SE70 the following values are displayed on the operating display: 
1st line    DC link current actual value r035 [%]  DC link voltage r006 [V]  Bus addr.
2nd line  #  DC link voltage actual value r037 [%]     
3rd line 
*
  DC link voltage setpoint r036 [%]     
4th line    Operating state r001     
 
The following parameters affect the function of the OP1S or of the interface SST1: 
P050 (language selection), P051 (access level), P053 (parameterization enable), P054 (OP backlighting), P683 
to P687 (interface settings) 
 
Control bits of the operator panel OP1S: 
(See also the operating instructions for the OP1S) 
Communication between the OP1S and the SIMOVERT device is performed via the interface G-SST1 (RS485) 
using the GPI protocol. 
By pressing the appropriate key on the OP1S, it is possible to execute functions. The OP1S sets the 
appropriate control word bit in PZD word 1 by means of transmission by the GPI protocol. (For details of the 
control word bits, see Chapter 4.3.1.1) 
For activation of the required function, parameterization as shown in the table below is required. 
Key on OP1S  Function  Bit in PZD word 1  Activation by 
On/off key (I / 0)  ON / OFF1  Bit 0  P554 = 2001 
Reset Acknowledgment *
)
  Bit 7  P565, P566, or P567 = 2001 
Jog  Jogging  Bit 8  P568 = 2001 
Reversal U
d
 reduction  Bit 11  P571 = 2001 
 Regenerative 
feedback enable 
Bit 12  P572 = 2001 
*
)
  Acknowledgment of the fault messages using the <Reset> key of the OP1S is only possible in the operating 
display, i.e. the operating display must first have been selected by pressing the <Reset> key (several times). 
Independently of that, acknowledgment is always possible by pressing the <P> key on the PMU. 
NOTE 
The predecessor of the OP1S (the OP1) cannot be used with software version V4.0 and higher because of its 
differing coupling mechanisms! The OP1S, however, is a suitable replacement for the OP1 if used with older 
device software. 