fåëí~ää~íáçå
10 oÉîáëáçå=MP=G=fkpq^iiqflk=fkpqor`qflkp=Ua^=G=USNJVOTPKV=
! Check transport units for condensation every 4 weeks.
! If the inside of the packing or parts of the switchgear show condensation: Remove
the packing, dry the switchgear and the packing. Refit the packing.
Outdoor storage The storage place must have the following characteristics:
Protected against rain water
Protected against flooding as well as melting water from snow and ice
Protected against pollution and vermin (e.g. insects, mice, rats)
Even floor to enable stable storage
Floor with adequate load-bearing capacity
Sufficient size to enable clearly arranged storage
! Place transport units on planks or square timber for protection against floor humidity.
! Store transport units in such a way that they can be taken out later in the correct
order for installation.
! After 6 months of storage, unpack the transport units and store them in closed
rooms, or regenerate the seaworthy packing (see below).
Regenerating the seawor-
thy packing
After 6 months of storage, the protection of the seaworthy packing is exhausted. If the
transport units still need to be stored outdoors, the seaworthy packing must be
regenerated.
! If there is no sufficient knowledge about professional regeneration of the packing:
Ask for expert personnel via the competent Siemens Service Centre.
! Open the packings.
! Renew desiccant bags.
! Refit the packings so as to reach full protection: Weld the PE protection sheeting
hermetically tight and rebuild the seaworthy crates completely.
5.5 Tools/auxiliary means
Before starting to work on the switchgear, provide the tools/auxiliary means required:
Vacuum pump (e.g. DILO type B048R01), DN8 connection
Dew-point meter (e.g. DILO type 3-035-R001), DN8 connection
Percentage meter (z. B. DILO type 3-027-R002), DN8 connection
Leakage detector (e.g. CPS type LS790)
•SF
6
-gas filling device (type 3-393-R001)
Vacuum cleaner with flexible and thin tube
1 set roller pads
Round-steel bars; diameter: 25 mm, length: 1600 mm for double panel + 600 mm for
each additional panel
Chain with transport shackles
Roller crowbars
Reinforcing bars
Racks (crank winch)
Hydraulic jack (2 to 3 t, for vertical and horizontal stroke)
Emery paper (K 360)
Step-ladder
Cable drum 220V~
•Drill
Torque wrench 8 – 20 Nm, 20 to 70 Nm