5.4 Intermediate storage
Storage in closed rooms The following switchgear parts must be stored in closed rooms:
• Unpacked parts
• Transport units which are not packed in seaworthy crates
The storage room must have the following characteristics:
• Well-ventilated
• Free of dust
• Dry and protected against flooding
• Relative humidity should not exceed 50%
• Protected against vermin (e.g. insects, mice, rats)
• Even floor to enable stable storage
• Floor with adequate load-bearing capacity
• Sufficient size to enable clearly arranged storage
! Do not unpack small parts to avoid corrosion and loss.
! Store transport units in such a way that they can be taken out later in the correct
order for installation.
! Provide for sufficient ventilation in heated storage rooms.
DANGER!
Risk of injury and damage to the stored goods if the storage surface is overloaded or
the transport units are stakked.
! Observe the load-bearing capacity of the floor.
! Do not stack the transport units.
DANGER!
Fire risk!
! No smoking.
! Keep fire extinguishers in a weatherproof place and mark their locations.
! Identify location of the fire extinguisher.
ATTENTION!
Supplied desiccant bags lose their effectiveness if they are not stored in the
undamaged original packings.
! Do not damage or remove packing of desiccant bags.
! Do not unpack desiccant bags before use.
ATTENTION!
The transport units may be damaged if these are stored outdoors without seaworthy
packing (seaworthy crate).
! Store transport units outdoors in seaworthy packing (seaworthy crate) only.