EasyManua.ls Logo

Siemens 8DA - 5.6 Aligning the Switchgear; 6 Assembling the Switchgear

Siemens 8DA
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
=USNJVOTPKV=G=fkpq^iiqflk=fkpqor`qflkp=Ua^=G=oÉîáëáçå=MP 13
fåëí~ää~íáçå
! Check the gas pressure in the compartments pre-filled at the factory on the
associated gas pressure indicators. The temperature-dependent limit values must
not be underflown.
! If the filling pressure is too low: Do not assemble the part of the switchgear
concerned and inform the regional Siemens representative concerned.
Fig. 5: Gas pressure indicators at the panel
a
Gas pressure indicators for the bus-
bar compartments (number accor-
ding to the design of the busbar
system)
s
Gas pressure indicator for the cir-
cuit-breaker housing
Fig. 6: Gas pressure indicators at the panel
a
Minimum permissible gas pressure
(signalling contact)
s
Actual gas pressure
d
Maximum permissible gas pres-
sure (signalling contact)
DANGER!
Operation with incorrect SF
6
-gas pressure can destroy parts of the switchgear.
! Do not install or put the switchgear into operation with incorrect SF
6
-gas pressures.