Description
34 Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * 500-8067.9
Indications VOIS, VOIS R+,
CAPDIS -S1+/-S2+
Indicatio
n
VOIS+, VOIS R+ CAPDIS-S1+ CAPDIS-S2+
L1 L2 L3 L1 L2 L3 L1 L2 L3
A0 Operating voltage not present (CAPDIS-S2+)
A1 Operating voltage present
A2 - Operating voltage not present
- Auxiliary power not present (CAPDIS-S2+)
A3 Failure in phase L1, operating voltage at L2 and L3
(for CAPDIS-Sx+ also earth-fault indication)
A4 Voltage (not operating voltage) present
A5 Indication: "Device-Funtion-Test" passed
A6 Indication: "ERROR" e.g. in case of missing auxiliary
voltage (CAPDIS-S2+, error indication M4)