8 Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * 500-8067.9
Description
5 Features
Typical uses 8DJH switchgear is used - even under severe ambient conditions - for power distribution
in secondary distribution systems, such as
Industrial distribution systems
Consumer and transfer substations
It is available for rated voltages up to 24 kV and rated currents of the feeders up
to 630 A.
Technology Factory-assembled, type-tested, metal-enclosed switchgear for indoor installation
Individual panels and/or panel blocks can be freely combined to a switchgear assembly
Circuit-breaker panels with maintenance-free indoor vacuum circuit-breakers for rated
voltages from 7.2 to 24 kV
Hermetically welded switchgear vessel, made of stainless steel, with welded-in
bushings for electrical connections and mechanical components
Insulating gas SF
6
Maintenance-free
Climate-independent
Three-position switch-disconnector with load-break and make-proof earthing function
Circuit-breaker with vacuum interrupters and integrated three-position disconnector
with make-proof earthing function
Cable connection for bushings with outside cone
Installation and extension without gas work
Comprehensive special equipment or accessories
Ecological manufacture and recycling

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens 8DJH Series and is the answer not in the manual?

Siemens 8DJH Series Specifications

General IconGeneral
Insulation mediumSF6 gas
EnclosureMetal-enclosed
TypeGas-insulated switchgear
Operating mechanismSpring mechanism
DimensionsVaries depending on configuration
WeightVaries depending on configuration