Description
38 Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * 500-8067.9
Indicator type
1)
Reset Remote reset: Automatic reset after
return of auxiliary
voltage supply
Pickup values Pickup values Option: Remote
indication as
A: By auxiliary voltage Short-circuit current I
k
(A)
Earth-fault current
I
E
(A)
W (passing
contact =
standard)
manually automatically
after
B: Via NO contact
(floating)
Standard, other values
on request
Standard, other
values on request
D (maintained
contact =
option)
Short-circuit indicator
ALPHA M
5)
x - - - 400, 600, 800, 1000 - W, D
ALPHA E
5)
x 2 h or 4 h A (12-60V AC/DC) - 400, 600, 800, 1000 - W, D
GAMMA 5.0
2) 5)
x 4 s after return of
power supply
- x (50 Hz, 230 V AC) 400, 600, 800, 1000 - W, D
2 h or 4 h
KA-Opto F
3) 5 8))
x after 2 h or 4 h B (1NO) - 400, 600, 800, 1000 - W, D
SIGMA x after 1, 2, 4, 8 h B (1NO) - 300, 400, 600, 800,
1000
-W, D
SIGMA ACDC
2)5)
x after 1, 2, 4, 8 h B (1NO) x (adjustable) 300, 400, 600, 800,
1000
-W, D
IKI-20-B1
6)
x after 2 h or 4 h B (1NO) - 400, 600, 800, 1000 - W, D
IKI-20-T1
6)
x after 2 h or 4 h B (1NO) x (50/60 Hz,
110-230 V AC)
400, 600, 800, 1000 - W, D
Earth-fault/short-circuit indicator
EKA-3
4)5)
- - - x (50 Hz, 230 V
AC)
4)
450 40, 80, 160 W, D
SIGMA F+E
5)
x after 1, 2, 4, 8 h B (1NO) - 300, 400, 600, 800,
1000
adjustable W, D
SIGMA F+E
5)
ACDC
x after 1, 2, 4, 8 h B (1NO) x (adjustable) 300, 400, 600, 800,
1000
adjustable W, D
DELTA E
5)
x after 2 h or 4 h A (12-60 V AC/DC) - 400, 600, 800, 1000 200 W, D
KA-Opto F+E
5)
x after 2 h or 4 h B (1NO) - 400, 600, 800, 1000 40, 60, 80 W, D
IKI-20-B1
6) 7)
x after 2 h or 4 h B (1NO) - 400, 600, 800, 1000 10% or 25% of I
K
W, D
IKI-20-T1
6) 7)
x after 2 h or 4 h B (1NO) x (50/60 Hz,
110-230 V AC)
400, 600, 800, 1000 10% or 25% of I
K
W, D
Earth-fault indicator
EKA-3/1
2) 4) 5)
- - - x (50 Hz, 230 V AC)
4)
- 40, 80, 160 W, D
CN-E
5)
x after 1, 2, 4, 8 h B (1NO) - - adjustable D
IKI-20-T1
6) 7)
x after 2 h or 4 h B (1NO) x (50/60 Hz,
110-230 V AC)
- 30, 55, 80, 100 W, D
1)
Further types on request.
2)
External auxiliary voltage required (120 V AC or 240 V AC).
3)
Power supply required for the LED indication (indication by means of an integrated battery or 12 V AC to 60 V AC voltage).
4)
External auxiliary voltage required (230 V AC, 50 Hz), device with integrated battery (capacity approx. 10 h).
5)
Make Horstmann.
6)
Make Kries Energietechnik.
7)
Ring-type sensor: d = 110 mm.
8)
With 3 LED indications.