10
Select Termination:
The RS485 topology must always be terminated using wave resisters.
They can be enabled or disabled here.
11
Select Restart:
After you are done entering settings; restart the controller using this 
command.
Extra
Modbus comm is the alarm object and settings like alarm class etc. for 
Modbus related alarms can be changed here.
After restarting, the internal Modbus RTU will be configured and ready to be used.
Generally speaking, the controller must always be restarted using “Restart” or by 
switching the power supply to the unit off and on after making changes in order for 
the new settings to be valid.
Settings other than those described above have nothing to do with a Modbus RTU 
operated as a slave and should therefore not be changed.
   
   
Short Manual for Climatix Control System [v. 2.14.10, 2.14.20, 2.14.30 & 2.14.40]
SMCX.130215.02GB Page 25