5.  Save and restore commissioning/factory 
settings
After you have entered your settings and adjustments you should save the 
parameters and settings in both the internal memory of the Climatix controller and in 
the SD memory in order to be able to restore them after a possible loss of data.
5.1  Save
5.1.1  Commissioning settings
Main menu > System overview > Save/Restore >
Select Save comm.settg. > Execute. Valid settings are saved in the internal memory 
of the main unit.
5.1.2  Settings to the SD memory
Main menu  > System overview > Save/Restore >
Insert an SD memory card in the memory card reader of the main unit. 
Select Save param.to SD > Execute. Valid settings are saved in the SD.
Caution! Already existing parameters in the SD card will be written over with the new 
ones.
5.2  Restore
5.2.1  Commissioning settings
Main menu  > System overview > Save/Restore >
Select Restore comm.settg. > Execute. The latest saved settings will be restored 
from the internal memory in the main unit to active applicable settings.
5.2.2  Settings from the SD memory
Main menu  > Configuration > Konfiguration via > Download 
RESTART - The unit will restart by itself when the option is changed from HMI to 
Download or vice versa. Whe the unit has started again, proceed to: 
Main menu  > System overview > Save/Restore >
Insert the SD memory card with the saved parameters in the memory card reader of 
the main unit. Select Load param.from SD > ExecuteFull. The saved settings on the 
SD card will be loaded to active valid settings in the controller. After this is done, a 
restart is required; 
Main menu  > System overview > Save/Restore > Restart.
5.2.3  To restore the factory settings
If you need to reinstate the settings the unit was supplied with from the factory, you 
can choose to restore the factory settings as follows:
Main menu  > System overview > Save/Restore >
Select Restore factory settg. > Execute. The saved factory settings in the internal 
memory will then be loaded to the active valid settings in the controller. 
RESTART - The will restart itself after you have selected Execute.  
After this automatic restart, restart the system one more time; 
Main menu > System overview > Save/Restore > Restart.