Properties / services
1.3 Communication services
CP 343-1 Lean
10 Manual, 10/2012, C79000−G8976−C198−07
New program block FB10 AG_CNTEX for connection diagnostics
Configuration of the IO devices in the STEP 7 "I-device" dialog box (and as previously
using a GSDML file)
Functional enhancements of the CX10 with firmware version V3.0 - regardless of the configuration
tool used
Advanced Web diagnostics (HTTP access) with the following additional options:
Diagnostics of S7 connections
Module identification
Expansion of Web diagnostics for The "Shared device" function
Update center of Web diagnostics with the following functions:
Downloading firmware via the Web (HTTP access)
Downloading of language files for diagnostics buffer texts in STEP 7 format for new
modules in the rack and for changing the language
SNMP: Support of the MRP Monitoring MIB
Enhanced functions of earlier firmware versions and predecessor modules
You will find an overview of the earlier firmware versions and predecessor modules in the
version history of the Industrial Ethernet CPs on the Internet pages of Siemens Automation
Customer Support under the following entry ID:
56699406 (http://support.automation.siemens.
com/WW/view/en/56699406)
You will find information about the characteristics of the individual firmware versions on the
Internet pages of Siemens Automation Customer Support under the following entry ID:
43409748 (http://support.automation.siemens.
com/WW/view/en/43409748)
> Entry list > Entry type "Updates"
1.3 Communication services
The CP supports the following communication services:
PROFINET IO
PROFINET IO allows direct access to IO devices over Industrial Ethernet.
PROFINET IO device
Integration of the SIMATIC S7-300 automation system via the CP as an intelligent
PROFINET IO device (I-device).
Shared device
Individual submodules of the CP (IO device) can be assigned up to two PROFINET IO
controllers in STEP 7 V5.5.
Note the information on configuring PROFINET IO systems with shared IO devices in
the "PROFINET System Description", see references, /13/ (Page 63).