LEDs
CP 343-1 Lean
26 Manual, 10/2012, C79000−G8976−C198−07
LEDs for displaying the operating mode
The different combinations of the LEDs on the front panel indicate the status:
Table 4- 1 LEDs: SF, BF, RUN, STOP
SF(red) BF (red) RUN (green) STOP (yellow) CP operating mode
-
Starting up after power "ON"
or
Stopped (STOP) with errors
In this state, the CPU or intelligent modules in the
rack remain accessible using PG functions.
Starting up (STOP → RUN)
Running (RUN)
Stopping (RUN → STOP)
Stopped (STOP)
In STOP mode, configuring and performing
diagnostics on the CP remain possible.
-
- - Duplicate IP address detected
-
- The CP is configured as a PROFINET IO device;
there is no data exchange with the PROFINET IO
controller.
Running (RUN) with error. Possible causes:
Event display in conjunction with the MRP
function. The CP diagnostics buffer provides
detailed information.
or
Extended port diagnostics reports an error.
Examples:
Current port setting (transmission medium,
duplex) does not correspond to the
configuration.
Port interconnection does not correspond to
the configuration.
Loading using the Firmware Loader is active. *
)
Firmware activation after loading using the Firmware
Loader is active. *
)
Firmware was successfully downloaded. *
)
Firmware download aborted. *
)
Module fault / system error
*
)
Does not apply to loading via the update center in Web diagnostics.