SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the maximum output frequency for resonance damping for V/f control.
Resonance damping is inactive above this output frequency.
Dependency: Refer to: p1338, p1339
Note: For p1349 = 0, the changeover limit is automatically set to 95 % of the rated motor frequency - however, to a max.
of 45 Hz.
Description: Sets whether the voltage is continuously increased during the magnetizing phase (p1350 = 1, On) or whether it
jumps directly to the voltage boost (p1350 = 0, Off).
Value: 0: Off
1: On
Note: The settings for this parameter have the following advantages and disadvantages:
0 = off (jump directly to voltage boost)
Advantage: Flux is established quickly -> torque is quickly available
Disadvantage: The motor can move while it is being magnetized
1 = on (voltage is continually established)
Advantage: The motor is unlikely to rotate
Disadvantage: The flux is established slower -> torque is available later
Description: Sets the configuration for the closed-loop speed control.
Note: Re bit 01:
When the bit is set, the I component of the speed controller is kept when changing into the open-loop controlled
mode.
p1349[0...n] V/f mode resonance damping maximum frequency / Vf res_damp F_max
Access level: 4 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]
p1350[0...n] Soft starting / Soft starting
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: DDS, p0180
Min Max Factory setting
0 1 0
p1400[0...n] Speed control configuration / n_ctrl config
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Min Max Factory setting
- - 1000 0000 0010 0001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Automatic Kp/Tn adaptation active Yes No 6040
01 Encoderless vector control freeze I comp Yes No 6040
05 Kp/Tn adaptation active Yes No -
06 Free Tn adaptation active Yes No -
14 Torque pre-control Always active For n_ctrl enab -
15 Encoderless vector control, speed pre-con-
trol
Yes No 6030