Siemens CU230P-2 HVAC - Fig. 2-39 9210 - Send telegram, Predefined Connection Set (p8744 = 1)

Siemens CU230P-2 HVAC
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
Function diagrams
2-483
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Fig. 2-39 9210 – Send telegram, Predefined Connection Set (p8744 = 1)
- 2441 -
Function diagram
87654321
FP_2441_97_51.vsd
PROFIdrive / PROFIBUS
G120 CU230P-2 DP
29.10.2009 V4.3
STW1 control word interconnection (p2038 = 2)
<1>
STW1.0
STW1.1
STW1.2
STW1.3
STW1.4
STW1.5
STW1.6
STW1.8
STW1.9
STW1.11
STW1.12
STW1.13
STW1.14
STW1.15
STW1.7
STW1.10
p0848[0] = r2090.2
p0852[0] = r2090.3
p1140[0] = r2090.4
p1141[0] = r2090.5
p1142[0] = r2090.6
p2103[0] = r2090.7
-
-
p0854[0] = r2090.10
p1113[0] = r2090.11
-
-
-
p0810[0] = 2090.15
<3>
p0840[0] = r2090.0
p0844[0] = r2090.1
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2546.1]
-
-
[2501.3]
[2505.3]
-
-
-
-
[2501.3]
[2501.3]
[3060] [3070] [3080]
[3060] [3070]
[3060] [3070] [3080]
[8060]
-
-
[2501]
[3040]
-
-
-
[8565]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
<2>
<2>
<1>
Signal targets for STW1 in Interface Mode VIK-NAMUR (p2038 = 2)
Signal
Meaning
Interconnectio
n parameters
[Function diagram]
internal control
word
[Function diagram]
signal target
Inverted
= ON (pulses can be enabled)
0 = OFF1 (braking with ramp-function generator, then pulse cancllation & ready-to-power-up)
1 = No OFF2 (enable is possible)
0 = OFF2 (immediate pulse cancellation and power-on inhibit)
1 = No OFF3 (enable is possible)
0 = OFF3 (braking with the OFF3 ramp p1135, then pulse cancellation and power-on inhibit)
1 = Enable operation (pulses can be enabled)
0 = Inhibit operation (cancel pulses)
1 = Operating condition (the ramp-function generator can be enabled)
0 = Inhibit ramp-function generator (set the ramp-function generator output to zero)
1 = Enable the ramp-function generator
0 = Stop the ramp-function generator (freeze the ramp-function generator output)
1 = Enable setpoint
0 = Inhibit setpoint (set the ramp-function generator input to zero)
= Acknowledge faults
Reserved
Reserved
Reserved
Reserved
Reserved
1 = Control via PLC
1 = Dir of rot reversal
1 = CDS selection
Used in telegram 20.
Bit 10 in STW1 must be set to ensure that the drive accepts the process data.
Sequence control
Sequence control
Sequence control
Sequence control
<3>
Interconnection is not disabled.