Table A-1 Diagnostic messages, their meaning and possible remedies
Diagnostics message Channel
error type
(CET)
Extended
channel
error type
(CET)
Assignment Meaning Remedy
Configuration error:
Station Stop – No
server module
0x0602 0x0693 Configura‐
tion
No server module was present
during power-up of an
ET 200SP HA station.
Verify that the server mod‐
ule is correctly installed in
the rack.
Configuration error:
Station Stop – Mod‐
ule parameter <po‐
tential group> errors
or incorrect terminal
block present in real
slot <slot>
0x0602 0x0691 Configura‐
tion
The installed terminal block
does not match the configura‐
tion.
Ensure that a matching ter‐
minal block is installed.
Configuration error:
Permissible back‐
plane bus size excee‐
ded
0x0602 0x0698 Configura‐
tion
The total width of the installed
modules exceeds the permissi‐
ble assembly length of
1300 mm.
Verify that the backplane
bus configuration does not
exceed the permissible size.
The server module must be
the last module plugged in
(highest permissible slot
number: 58).
Configuration error:
Incorrect backplane
bus configuration in
slot <slot>
0x0602 0x0699 Configura‐
tion
The maximum current demand
of all plugged-in modules ex‐
ceeds 2100 mA.
The accompanying <slot> val‐
ue indicates the slot causing
the error.
Check the configuration of
the ET 200SP HA.
Configuration error:
Impermissible bus
adapter on interface
module
0x0602 0x069C Configura‐
tion
The installed bus adapter does
not match the configuration.
Verify that a matching bus
adapter is installed.
Configuration error:
No server module
0x0602 0x069E Configura‐
tion
The server module is pulled
during operation of an
ET 200SP HA station.
Ensure that the server mod‐
ule is correctly installed in
the rack.
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)