Note
The following LEDs indicate a short-circuit in the backplane bus supply or in the bus connection
supply:
LED PWR: On
LED RN, ER and MT: Off
6.2 Interrupts
Diagnostics interrupts
Diagnostic interrupts are used by the IM 155-6 PN HA to signal diagnostic messages as well
as maintenance events, see also appendix Diagnostics messages and maintenance events
(Page 31)
The IM 155-6 PN HA generates a diagnostic interrupt for the following events:
Faulty 24 V DC power supply
Module parameter errors or incorrect carrier present in real slot
Failure of redundancy partner
Redundancy partners have different hardware/firmware
Impermissible bus adapter on interface module
Incorrect bus adapter in redundancy partner
Defective retentive memory in bus adapter
Permissible backplane bus size exceeded
No server module
Diagnostics of I/O modules are forwarded by the IM 155-6 PN HA and depend on the respective
I/O module.
Maintenance messages
The IM 155-6 PN HA generates a maintenance message for the following events:
Different hardware/firmware in the redundancy partners
IO redundancy warning
Redundancy parameter assignment inconsistent
Retentive memory in carrier module defective
Defective retentive memory in bus adapter
Displays and interrupts
6.2 Interrupts
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA 23