The interface has the following technical properties:
Supply voltage 1L+ 24 V DC (SELV/PELV).
The supply voltage is fed via the carrier module.
The connection plug is included in the scope of delivery of the interface module.
PROFINET IO connection via BusAdapter (see following paragraph, "Accessories")
The interface supports the following functions:
Firmware update
I&M identification data
Pulling and plugging modules in RUN
Value status QI
IO redundancy
Time stamping
Multi Hot Swap (pulling/plugging of multiple I/O modules during operation)
Saving service data
Recording the value status of I/O modules
Reference temperature distribution
You can configure the interface with HW Config and integrate it into your system
Note
The IM 155‑6 PN HA cannot be pulled/plugged when the associated connector for the supply
voltage is plugged in.
PROFINET IO functions
The interface supports the following PROFINET IO functions:
Integrated BusAdapter with 2 ports
Supported Ethernet services: ping, arp, network diagnostics (SNMP)/MIB-2, LLDP-MIB and
MRP-MIB
Port diagnostics
Disabling of ports
Minimum update time of 250 µs
Device replacement without programming device (PG)
Reset to factory settings via PROFINET IO
System redundancy S2
System redundancy R1
Media redundancy (MRP)
Support of submodules on suitable I/O modules
Product overview
2.1 Properties
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
8 Manual, 05/2017, A5E39262148-AA