4 Configuration extensions
The KS 50-1 TCont configuration values are extended by the following settings
compared with the standard version
.
q
Protocol selection
In configuration menu othr, item Prot is available for definition of the
protocol to be used.
othr
Name Range Description Default
Prot Protocol selection for rear interface 1
0 MODBUS RTU
1 Protocol for tempering unit
2 Protocol for hot runner
q Output selection
Control of a pump can be selected via parameter PumPin the configuration menu
for OUT.1, OUT.2, OUT.3, OUT.5 or OUT.6 . The default is an active OUT.3.
OUT.1, OUT.2, OUT.3, OUT.5, OUT.6
Name Range Description Default
PuMP output pump 0
0 Not active
1 Active
q
Self-tuning start
For KS 50-1 TCont, the self-tuning behaviour during start-up was changed.
Self-tuning is suppressed during power-on and called up only when starting
control operation, if permitted (see OrEL).
Cntr
Name Range Description Default
Strt Self-tuning start 0
0 Manual self-tuning start via the front panel, or when starting
control operation, if permitted.
1 Manual self-tuning start via the front panel, when starting
control operation, if permitted, and when detecting
oscillation.
Configuration extensions
Operating note KS 50-1 TCont 11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Expert Series and is the answer not in the manual?

Siemens Expert Series Specifications

General IconGeneral
Control ModePID
Input TypeThermocouple, RTD, Analog
Output TypeRelay, Analog
Supply Voltage100-240 VAC, 24 VAC/VDC
DisplayLED
CommunicationRS485

Related product manuals