4 Configuration extensions
The KS 50-1 TCont configuration values are extended by the following settings
compared with the standard version
.
q
Protocol selection
In configuration menu othr, item Prot is available for definition of the
protocol to be used.
othr
Name Range Description Default
Prot Protocol selection for rear interface 1
0 MODBUS RTU
1 Protocol for tempering unit
2 Protocol for hot runner
q Output selection
Control of a pump can be selected via parameter PumPin the configuration menu
for OUT.1, OUT.2, OUT.3, OUT.5 or OUT.6 . The default is an active OUT.3.
OUT.1, OUT.2, OUT.3, OUT.5, OUT.6
Name Range Description Default
PuMP output pump 0
0 Not active
1 Active
q
Self-tuning start
For KS 50-1 TCont, the self-tuning behaviour during start-up was changed.
Self-tuning is suppressed during power-on and called up only when starting
control operation, if permitted (see OrEL).
Cntr
Name Range Description Default
Strt Self-tuning start 0
0 Manual self-tuning start via the front panel, or when starting
control operation, if permitted.
1 Manual self-tuning start via the front panel, when starting
control operation, if permitted, and when detecting
oscillation.
Configuration extensions
Operating note KS 50-1 TCont 11