5 System data
System logbook
Is the system logbook available and up-to-date?
Remote transmission
Are the telephone numbers and the names of the remote transmission recipients
up-to-date?
System disk
Is the system data disk available and up-to-date?
If configuration changes are made, then update the system disk. One disk remains
with the system and a copy is filed with the project-engineering department.
If no modifications are made, a new copy of the disk must be made every 5 years
in order to prevent loss of data through ageing.
The date of the new version must be recorded in the logbook.
Equipment program
Check the equipment program version printed on the EPROM label. Replace older
software versions with the latest if new functions and/or error corrections call for it.
Event memory
Check the content of the event memory and take the necessary counter-measures.
Replace all detectors in "Drift" conditions.
Change of use
Inspect all reported changes to the building, especially rooms with new utilization.
Make all necessary modifications to the FC700A system with regards to this
change.
Planned modifications
Check whether all modifications have been carried-out, e.g. changes to diagrams,
fire department plans?