Control terminal check
15
Siemens Building Technologies 007833_a_en_--.doc
Fire & Security Products 03.2004
8 Control terminal check
Hardware
Check conditions visually.
Earth connections
Repair damaged earth connections.
Labelling
Are the display equipment inscription strips correct and still clearly readable?
Performance check
Procedure:
1. Login by entering operating code.
2. Activate lamp test.
3. Check operation at PRESENT / ABSENT.
4. Switch 1 zone on/off.
5. Activate 1 ALARM, acknowledge and reset.
6. Activate 1 FAULT, acknowledge and reset.
7. Log-out.
Cleaning
Clean display window and front panel with mild soap. Do not use abrasive sol-
vents.