System performance check
17
Siemens Building Technologies 007833_a_en_--.doc
Fire & Security Products 03.2004
Interval in years
Check activation up to and including interface.
Fire control
installations
Check customer system shutdown operations (work charged
to the customer or carried out by the customer himself). Fix a
time schedule with the customer.
Emergency
operation
function
Activate ALARM with reset button depressed:
Collective lines with test probe (1 line per collective mod-
ule).
Addressable lines with 1 detector per line.
Check activation of remote transmission.
Verify indicators on emergency operation FT.
Check the functioning of the delay times V1 and V2.
Check of the delay time at mains failure.
Alarm activation by automatic fire detector set to ABSENT =
ALARM II.
Alarm activation by manual call point set to PRESENT and
ABSENT = ALARM II.
Verify the automatic switchover PRESENT / ABSENT using
event memory entry.
Check activation of remote transmission equipment with
ALARM II.
Alarm organi-
zation
Check WARNING level by activation of a zone via FT.
In emergency power operation mode, check all alarm devices
according to status level:
WARNING
ALARM I
ALARM II
REMOTE ALARM
FAULT
Check the activation periods (if programmed) for PRESENT
an ABSENT modes.
Alarm equip-
ment
Check the remote transmission equipment according to in-
structions provided by the remote transmission equipment
supplier.
9.2 Intervals for the detector overhaul at factory
Heavy-duty applications in industrial areas (chemical processes, conveyor belts
for raw material etc.) were not taken into consideration in the standard values
below. The values have to be adapted accordingly.
HI62x will not be overhauled at the factory.
All detectors must be activated during "Detector test mode" after detector over-
haul.
Application range Risk Interval in years
Addressable Synova™
600 detectors
Clean
Standard
High
6
5
Moderate soiling
Standard
High
5
4
Collective Synova
600 detectors
Clean
Standard
High
5
4
Moderate soiling
Standard
High
3
2
Definitions:
Application range "Clean", e.g.:
EDP rooms
Offices
Theatre, museum, churches, hotel guest rooms
Meeting halls, exhibition halls
Department stores, shopping halls
Hospitals
Application range "Moderate soiling", e.g.:
Storage and stock rooms, warehouses
Production halls and assembly areas
Cable ducts, risers, elevated floors
Wood industry, textile industry
High risk, e.g.:
Rooms and areas with high value concentration or sensitive work processes.