4
Planning
Operating modes
40
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
4.2.1 Parameter Sets
The following information applies to the 'Automatic: switches between blue and
blue-red based on ratio' mode.
FDA241
Set
No.
Sensitivity [%/m]
Comment
Inspect
Prealarm
Fire 1
Fire 2
0 0.07 0.10 0.15 20 default
1 0.03 0.04 0.05 2 -
2 0.03 0.045 0.06 2.5 -
3 0.04 0.055 0.07 3 -
4 0.05 0.075 0.10 4 -
5 0.07 0.10 0.15 5 -
6 0.08 0.14 0.20 6 -
7 0.18 0.28 0.40 8 -
8 0.30 0.50 0.70 10 -
9 0.40 0.70 1.00 15 -
10 0.80 1.40 2.00 20 -
FDA221
Set no.
Sensitivity [%/m]
Comment
Prealarm
Fire 1
Fire 2
0 0.50 0.70 20 default
6 0.14 0.20 6 -
7 0.28 0.40 8 -
8 0.50 0.70 10 -
9 0.70 1.00 15 -
10 1.40 2.00 20 -