Commissioning
7
Functional testing of the system
83
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
7.3 Functional testing of the system
7.3.1 Functional testing of the system with an addressed
detector line (FDnet/C-NET)
NOTICE
Accidental triggering of an alarm
Using smoke or aerosols for testing purposes may trigger an alarm
unintentionally.
Make sure no alarm is sent to the fire brigade during the test.
Communication transponder FDCC221S is installed.
A smoke stick/aerosol spray is available.
1. Switch the relevant element on the fire detection system to test mode and
follow the description in the 'Testing the detector" chapter of the fire detection
system documentation.
The operating indicator flashes.
2. Move the smoke/aerosol toward an aspirating hole in the pipe system.
Select an aspirating hole that is a long distance away if you want to test the
response time as well.
3. Check whether an alarm is indicated on the front indicator.
4. Check whether an alarm has been transmitted to the fire control panel.
5. Wait until the smoke indicator has dropped to no more than 5 LEDs.
6. Reset the alarm on the fire control panel and quit test mode.
That is the end of the test.

Table of Contents

Other manuals for Siemens FDA2 1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDA2 1 Series and is the answer not in the manual?

Siemens FDA2 1 Series Specifications

General IconGeneral
BrandSiemens
ModelFDA2 1 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals