Mounting / Installation
5
Preparatory work
51
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
5.1.4 Removing and installing the housing cover when the power
supply is switched on
NOTICE
Electrostatic discharge
Damage to electronic components in the aspirating smoke detector
When working on the open aspirating smoke detector, use anti-static floor
mats and anti-static work surfaces.
Ground yourself immediately before opening the housing, e.g. by touching a
ground point or wearing an anti-static belt.
NOTICE
Accidental triggering of an alarm
Triggering a false alarm
When the housing cover is opened, the buzzer sounds. The relay outputs
remain active and the 4…20 mA analog output has been switched to fault
(0.5 mA).
If the button is pressed, the buzzer switches off and the relay
outputs are deactivated. The 4…20 mA analog output remains on fault.
Closing the housing cover automatically reactivates the relay outputs and the
4…20 mA analog output switches to normal operation.
When the housing cover is removed, you have access to:
The fixing screws
The cable entry
All the mechanical components
The electrical connections
The rear of the front indicator

Table of Contents

Other manuals for Siemens FDA2 1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDA2 1 Series and is the answer not in the manual?

Siemens FDA2 1 Series Specifications

General IconGeneral
BrandSiemens
ModelFDA2 1 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals