17.3 Time table and settings for program sequence PME73.830...  
Type  Times in seconds 
PME73.830... 
tw 
TSA 
max. 
t1 
P225 
4) 
min. 
t3 
P226 
min. 
t3n 
P257 
approx. 
t4 
P230
min. 
t5 
P232
min. 
t8 
P234 
5) 
min. 
t9 
P231 
approx. 
t10 
P224 
approx. 
t11 
P259 
approx. 
t12 
P260 
approx. 
t22 1) 2)  3) 
td1 
td2 
min. 
td3 
td4 
max. 
Requirement 2.5  3  30  6  2.5  9 8.5 15  3  15  300  300 t9+1 --- --- --- 10  3 
Factory setting  ---  t3n+0.45  29.106+2.1 6.174 2.205+0.3 9.408 8.82 19.404 2.646 13.818 300.762 300.762  ---  --- ---  ---  10.29 2.646 
Max. 2.5  14  1237+2.1  37.485  13.23+0.3  74.97  74.97 1237  74.97  13.818  1237  1237  ---  1 0.45 0.45 37.485 2.646 
Min. ---  ---  0+2.1  1.029  0+0.3  3.234 2.058 0  0  0  0  0  --- 0.3 0.3 --- 1.029 0 
Step size  ---  ---  4.851  0.147  0.147  0.294  0.294  4.851 0.294  0.294  4.851  4.851  ---  --- ---  --- 0.147 0.147 
 
Function parameter  Parameter number  Factory setting 
Repetition in the event of loss of flame during operation 
<2: None 
= 2: 1 x 
P240 0 
Valve proving 
0: Inactive 
1: Active 
P241.00 1 
Valve proving 
0: During prepurge time  
1: During postpurge time 
P241.01 1 
Valve proving 
0: According to P241.01 
1: During prepurge time and postpurge time 
P241.02 0 
Actuator position during prepurge time and postpurge time 
0: Purging in low-fire 
1: Purging in high-fire 
P515 1 
 
Legend 
 
tw  Waiting time  t10  Specified time air pressure switch state message (timeout) 
TSA  Safety time  t11  Opening time of actuator (timeout) 
t1 Prepurge time  t12 Closing time of actuator (timeout) 
t3  Preignition time  t22  2nd safety time 
t3n  Postignition time (P257 +0.3 seconds)     
t4  Interval: End of safety time - fuel valve 1 ON  td1  Test atmospheric pressure 
t5  Interval: Pilot valve OFF - load controller release  td2  Test gas pressure 
t8  Postpurge time  td3  Test space filling 
t9  Interval: Fuel valve 1 ON - pilot valve OFF  td4  Test space evacuating 
 
1) 
Response time to a change of signal by air pressure switch (opens) and response time in the event of loss of flame 
2)  Response time to a change of signal by inputs (e.g. pressure switch-min) 
3)  Flame detection time 
4)  Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON), after mains ON, with lockout, P234 (postpurge time) = 0 (postpurging) or P241.01 = 0 
5)  Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON) and P234 (postpurge time) >0 (postpurging) and P241.01 = 1