EasyManua.ls Logo

Siemens LME71.000A1 - 2 System Makeup;Function Description

Siemens LME71.000A1
245 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21/245
Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 2 System makeup/function description 29.11.2011
2 System makeup/function description
The LME7... is a microprocessor-based burner control with matching system
components for the control and supervision of forced draft burners of medium to high
capacity.
LME7… are used for the startup and supervision of 1- or 2-stage forced draft burners in
intermittent operation. The flame is supervised with an ionization probe, optionally with
flame detector QRA2..., QRA4.U or QRA10....
- Gas burner controls to EN 298 : 2003
- Oil burner controls to EN 230 : 2005
- For forced draft gas burners to EN 676
- For forced draft oil burners to EN 267
Integrated in the LME7... basic unit are:
Burner control
BCI for connection a display or PC
Only LME72.../LME73...: Control for one actuator
Lockout reset button (info button)
3 multicolor signal lamp LED for operations and fault notifications
Optional: Analog inputs for load controller DC 0...10 V, DC 0/4...20 mA, 0...135
3 x 7-segment display for service, fault and operating state information
Interface for program module
Figure 2: Example: Modulating gas burner

Table of Contents