18.5 Time table and settings for program sequence PME73.831...  
Type  Time in seconds 
PME73.831...  tw 
TSA 
max. 
t1 
P225 
4)
 
min. 
t3 
P226 
min. 
t3n 
P257 
approx. 
t4 
P230
min. 
t5 
P232
min. 
t8 
P234 
5)
 
min. 
t9 
P231 
approx. 
t10 
P224 
approx. 
t11 
P259 
approx. 
t12 
P260 
approx. 
t22 
P254
1) 
 
2) 
 
3) 
td1 
td2 
min. 
td3 
td4 
max. 
Requirement  2.5  3  30  2  2.5  3  8.5  0  3  12  65  65  t9+P254(1/3)  ---  ---  ---  10  3 
Factory setting  ---  t3n+0.45  29.106+2.1  2.058  2.205+0.3  3.234  8.82  0  2.94  12.054  67.914  67.914  ---  1  ---  ---  10.29  2.646 
Max.  2.5  14  1237+2.1  37.485  13.23+0.3  74.97  74.97  1237  74.97  13.818  1237  1237  ---  3  0.45  0.45  37.485  2.646 
Min.  ---  ---  0+2.1  1.029  0+0.3  3.234  2.058  0  0  0  0  0  ---  1  0.3  ---  1.029  0 
Step size  ---  ---  4.851  0.147  0.147  0.294  0.294  4.851  0.294  0.294  4.851  4.851  ---  ---  ---  ---  0.147  0.147 
 
Type  Time in seconds 
PME73.831... 
 
P259.01 
approx. 
 
P259.02 
approx. 
Requirement  15  15 
Factory setting  14.994  14.994 
Max.  37.485  37.485 
Min.  0  0 
Step size  0.147  0.147 
 
Function parameter  Parameter number  Factory setting 
Repetition in the event of loss of flame during operation 
<2: None 
= 2: 1 x 
P240  0 
Valve proving 
0: Inactive 
1: Active 
P241.00  1 
Valve proving 
0: During prepurge time  
1: During postpurge time 
P241.01  0 
Valve proving 
0: According to P241.01 
1: During prepurge time and postpurge time 
P241.02  0 
Response time flame error or air pressure switch error 
0: 1 second 
1: 3 seconds 
P254  0 
Intermittent operation after 24 hours of continuous operation 
0: OFF 
1: ON 
P239  1 
Actuator position during prepurge time and postpurge time 
0: Purging in low-fire 
1: Purging in high-fire 
P515  1