Building Technologies Division  Basic Documentation LME7...   CC1P7105en 
Infrastructure & Cities Sector  18 PME73.831…  29.11.2011 
Legend 
tw  Waiting time  t10 
Specified time air pressure switch state message (timeout) 
TSA  Safety time  t11 
Opening time of actuator (timeout) 
t1  Prepurge time  t12 
Closing time of actuator (timeout) 
t3  Preignition time  t22 
2nd safety time 
t3n  Postignition time (P257 +0.3 seconds)  td1 
Test atmospheric pressure 
t4  Interval: End of ignition safety time – fuel valve 2 ON  td2 
Test gas pressure 
t5  Interval: Pilot valve OFF – release of load controller  td3 
Test space is filled 
t8  Postpurge time  td4 
Test space evacuating 
t9  Interval: Fuel valve 2 ON – pilot valve OFF     
 
1) 
Response time to a change of signal by the air pressure switch (opens) and response time in the event of loss of flame 
2) 
Response time to a change of signal by the inputs (e.g. pressure switch-min) 
3) 
Flame detection time 
4) 
Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON), after power ON, with lockout, P234 (postpurge time) = 0 (postpurging) or P241.01 = 0 
5) 
Minimum time td1 + td2 + td3 + td4 if: Parameter P241.00 = 1 (ON) and P234 (postpurge time) >0 (postpurging) and P241.01 = 1 
 
P259.01  Actuator running time from ignition load to a position > low-fire 
P259.02  Actuator running time from low-fire to a position > ignition load