EasyManua.ls Logo

Siemens LME71.000A1 - Terminal rating Outputs

Siemens LME71.000A1
245 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31/245
Building Technologies Division Basic Documentation LME7... CC1P7105en
Infrastructure & Cities Sector 4 Technical data 29.11.2011
4.3 Terminal rating Outputs
Total contact loading:
Rated voltage AC 120 V
50/60 Hz
AC 230 V
50/60 Hz
Unit input current X3-04
(safety loop) from:
- Fan motor contactor
- Ignition transformer
- Fuel valves
Max. 5 A Max. 5 A
Individual contact loading:
Fan motor contactor X2-01 pin 3
Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz
Rated current 2 A
(15A max. 0.5 s)
2 A
(15A for max. 0.5s)
Power factor Cos 0.4 Cos 0.4
Alarm output X2-03/3
Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz
Rated current 1 A 1 A
Power factor Cos >0.6 Cos >0.6
Ignition transformer X4-02 pin 3
Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz
Rated current 2 A 2 A
Power factor Cos >0.4 Cos >0.4
Auxiliary output
Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz
Rated current 1 A 1 A
Power factor Cos >0,6 Cos >0,6
Output relay contact 2 pin 2 X2-09 pin 7
Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz
Rated current 1 A 1 A
Power factor Cos >0.4 Cos >0.4
Fuel valves/pilot valve X7-01 pin 3
Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz
Rated current 1 A 1 A
Power factor Cos >0.4 Cos >0.4
Fuel valves 1 X7-04 pin 4/fuel valve 2 X7-02 pin 3
Rated voltage AC 120 V 50/60 Hz AC 230 V 50/60 Hz
Rated current
- Valve proving inactive
2 A 2 A
- Valve proving active 1 A 1 A
Power factor Cos >0.4 Cos >0.4
Note:
When activating valve proving (e.g. on shutdown), the load on the valve
terminals is restricted. If the load is not reduced, the design lifetime is about
100,000 burner start cycles!
Safety valve X6-03 pin 3
Rated voltage AC 120 V
50/60 Hz
AC 230 V
50/60 Hz
Total current 1.5 A 1.5 A
Power factor Cos >0.6 Cos >0.6
Safety loop X3-04 pin 2, safety valve X6-03 pin 3, POC X2-02 pin 3
Rated voltage AC 120 V
50/60 Hz
AC 230 V
50/60 Hz
Total current 2 A 2 A
Power factor Cos >0.4 Cos >0.4

Table of Contents

Related product manuals